Item | Ignition Module |
Application | Boilers, Infrared And Tube Heaters, Laundry, LP/Natural Gas Furnaces, Ovens, Unit Heaters, Water Heaters |
Automatic Reset Time | 1 hr. |
Board Type | Non-Integrated Board |
Control Voltage | 24V AC |
Electrical Connection Type | 3/16" Quick-Connect |
Flame Sensor Current Output | 0.5 µA |
For Fuel Type | LP, Natural Gas |
Frequency | 50/60 Hz |
Igniter Warm Up Time | 90 sec. |
Ignition Cycle Time | 90 seconds (IP), 0 seconds (pre-purge), 0 seconds (inter-purge) | 4 seconds (DS), 30 seconds (pre-purge), 30 seconds (inter-purge) |
Lead Length | 5 1/2" |
Lock Out Time | 5 min. |
Low Voltage Protection | Low Voltage Protected |
Main Valve Current Output | 4A |
Maximum Operating Temperature | 175°F |
Minimum Operating Temperature | -40°F |
Number Of Retries | 1 |
Operating Temperature Range | -40°F to 175°F |
Pilot Valve Current Output | 2A |
Pre-purge Time | 45 sec. |
Product Type | Ignition Module |
Replacement For Oem Brand | AAON, ADC, Bakers Pride, Baso, Beckett, BKI, Blodgett, Bradford White, Camstat, Capable, Carrier, Cleveland, Crown Stream, Dexter, Duke, Fenwal, Frymaster, Garland, Goodman, Groen, Henny Penny, Hobart, Honeywell, ICM, Johnson Controls, Laars, Lennox, Lincoln, Lochinvar, Midco, Middleby, Modine, Picard, Pitco, Resideo, Reznor, Rheem, Roberts Gordon, Robertshaw, Snyder, Space Ray, Sunstar, Superior Radiant, Trane, UTEC, Utica-Dunkirk, Vulcan Hart, Weil McLain, White-Rodgers, York |
Replacement For Oem Part Number | 00-354447-00001, 00-857207-00001, 00-857207-00002, 025-27662-000, 025-27662-700, 025-29012-001, 025-29012-002, 025-29012-003, 025-29012-004, 025-42681-000, 031-01283-000, 03546, 05-162425-103, 05-162425-200, 05-162426-000, 05-162426-001, 05-162426-002, 05-162426-003, 05-162426-005, 05-162426-006, 05-162426-007, 05-162426-053, 05-162426-101, 05-162426-105, 05-162426-200, 05-162426-201, 05-162426-203, 05-162426-207, 05-162526-005, 05-169001-000, 05-169001-001, 05-169001-002, 05-169001-003, 05-169002-003, 05-169003-103, 05-169005-123, 05-169006-201, 05-169007-201, 05-169008-225, 05-169009-005, 05-169009-023, 05-169010-023, 05-169011-201, 05-169011-205, 05-169012-200, 05-169015-705, 05-169018-003, 05-203025-005, 05-203026-005, 05-272426-005, 05-272426-055, 05-272426-253, 05-279000-023, 05-279001-223, 05-279002-223, 05-279003-223, 05-279004-201, 05-279004-223, 05-279005-223, 05-296423-150, 05-296423-151, 05-296423-750, 05-296423-751, 05-296425-153, 05-296425-250, 05-296425-755, 05-296426-150, 05-296426-151, 05-296426-153 |
Replacement Type | OEM |
Standards | UL LISTED |
Thermostat Anticipator Setting | Thermostat Anticipator |